Specifications
We have obtained certificates of ISO9001,ISO14001 China's Electrical Product Safety Certification
Standard:
ASTM BS DIN GB
Application:
1. AAC are used in overhead power tranmission and distribution lines with various grade voltages.
2. Under the same weight, AAC is with higher DC resistance and lower costthan cooper conductor.
The data sheets below show the standards IEC61089:
Code Number
|
Nominal area
|
Stranding&
|
Approx
|
Approx
|
Breaking load
|
DC Resistance at 20
|
Wire
|
overall
|
weight
| ||||
Diameter
|
diameter
| |||||
mm 2
|
mm
|
mm
|
kg/km
|
kN
|
ohm/km
| |
10
|
10
|
7/1.35
|
4.05
|
27.4
|
1.95
|
2.8633
|
16
|
16
|
7/1.71
|
5.12
|
43.8
|
3.04
|
1.7896
|
25
|
25
|
7/2.13
|
6.4
|
68.4
|
4.5
|
1.1453
|
40
|
40
|
7/2.70
|
8.09
|
109.4
|
6.8
|
0.7158
|
63
|
63
|
7/3.39
|
10.2
|
172.3
|
10.39
|
0.4545
|
100
|
100
|
19/2.59
|
12.9
|
274.8
|
17
|
0.2877
|
125
|
125
|
19/2.89
|
14.5
|
343.8
|
21.25
|
0.2302
|
160
|
160
|
19/3.27
|
16.4
|
439.8
|
26.4
|
0.1798
|
200
|
200
|
19/3.66
|
18.3
|
549.7
|
32
|
0.1439
|
250
|
250
|
19/4.09
|
20.5
|
687.1
|
40
|
0.1151
|
400
|
400
|
37/3.71
|
26
|
1102
|
64
|
0.0721
|
450
|
450
|
37/3.94
|
27.5
|
1239.8
|
72
|
0.0641
|
500
|
500
|
37/4.15
|
29
|
1377.6
|
80
|
0.0577
|
560
|
560
|
37/4.39
|
30.7
|
1542.9
|
89.6
|
0.0515
|
630
|
630
|
61/3.63
|
32.6
|
1738.3
|
100.8
|
0.0458
|
710
|
710
|
61/3.85
|
34.6
|
1959.1
|
113.6
|
0.0407
|
800
|
800
|
61/4.09
|
36.8
|
2207.4
|
128
|
0.0361
|
900
|
900
|
61/4.33
|
39
|
2483.3
|
144
|
0.0321
|
1000
|
1000
|
61/4.57
|
41.1
|
2759.2
|
160
|
0.0289
|
1120
|
1120
|
91/3.96
|
43.5
|
3093.5
|
179.2
|
0.0258
|
1250
|
1250
|
91/4.18
|
46
|
3452.6
|
200
|
0.0231
|
1400
|
1400
|
91/4.43
|
48.7
|
3866.9
|
224
|
0.0207
|
1500
|
1500
|
91/4.58
|
50.4
|
4143.1
|
240
|
0.0193
|
没有评论: