H07V-K flexible wire

Application:                                                                                            
 Flexible insulated conductor used for laying in electric-installation tubes, under and on plaster installation in dry rooms and in closed installation conduits. Direct laying in cable guides is not permitted. Also applied for internal wiring of distribution and switching boxes equipment, same as for protective laying for lighting of nominal voltage up to 1000 V alternating current, or up to 750 V direct current against earth.  
Construction:           
1. Conductor:   bare copper conductor, fine wired stranded, class 5. acc. to IEC 60228 / HD 383 / DIN VDE 0295
2. Insulation: PVC compound TI1 acc. to IEC 60227-3 / HD 21.3 S3 / DIN VDE 00281 part 3   Conductor acc. to IEC 60446 i.e. EN 60446  , Colour(corresponding to DIN VDE 0293)                         
Temperature range:  
during installation:  +5 °C up to +70 °C,    fixed installed: -30 °C up to +70 °C, at short circuit of max. 5 s: up to 160 °C, ambient temperature at storage: up to 40 °C,
 Nominal voltage: Uο/U = 450/750 V,  Test voltage: 2500 V, Minimal inner bending radius: 4D for D < 8 mm, 5D for 8 - 12 mm ,  6D for D > 12 mm, Behaviour in fire: IEC 60332-1
Product Advantages:
1. The long-time permissible operation temperture of conductor shall not be higher than 70 or  90 centigrate.
2. Conductor maximum short circuit(not more than 5 seconds)temperature shall not be higher than 160 oC.
3. The power cable is not limited by drop in level when being laid, and the ambient temperature shall not be lower than 0 oC. 
4. Perfect chemical stability, resistant against acids, alkalis, grease and organic solvents, and flame. 
5. Light weight, perfect bending properties, installed and maintained easily and conveniently.
Parameter:
Dimensions – conductor cross-section
Construction of individual conductor
External diameter
Insulation thickness
Conductor resistance at 20 °C
Specific. el. resistance of insulation at 70°C
Cu weight
Cable weight
Packing*

nominal
min-max.
nominal
max
min.

approx.
mm²
n x mm
mm
mm
Ω/km
MΩkm
kg/km
kg/km
1,5
30 x 0,25
2,8 - 03,4
0,7
13,3
0,0100
14,4
20
c.100, c.200
2,5
50 x 0,25
3,4 - 04,1
0,8
7,98
0,0095
24,0
32
c.100
4
56 x 0,30
3,9 - 04,8
0,8
4,95
0,0078
38,4
46
c.100
6
84 x 0,30
4,4 - 05,3
0,8
3,30
0,0068
57,6
65
c.100
10
80 x 0,40
5,7 - 06,8
1,0
1,91
0,0065
96,0
115
c.100
16
128 x 0,40
6,7 - 08,1
1,0
1,21
0,0053
153,6
170
c.100
25
200 x 0,40
8,4 - 10,2
1,2
0,780
0,0050
240
260
CUT
35
280 x 0,40
9,7 - 11,7
1,2
0,554
0,0043
336
360
CUT
50
400 x 0,40
11,5 - 13,9
1,4
0,386
0,0042
480
515
CUT
70
356 x 0,50
13,2 - 16,0
1,4
0,272
0,0036
672
710
CUT
95
485 x 0,50
15,1 - 18,2
1,6
0,206
0,0036
912
940
CUT
120
614 x 0,50
16,7 - 20,2
1,6
0,161
0,0032
1152
1180
CUT
150
765 x 0,50
18,6 - 22,5
1,8
0,129
0,0032
1440
1600
CUT
185
944 x 0,50
20,6 - 24,9
2,0
0,106
0,0032
1776
2100
CUT
240
1225 x 0,50
23,5 - 28,4
2,2
0,0801
0,0031
2304
3015
CUT