300/500V Class 5 2X1.5MM copper /fire resistance PVC sheathed RVS cable ,

Copper core PVC insulated fire-resistant stranded flexible wire for connection

1. Application
     The product is applied to power plant with AC 300/300V and below, it is widely used in low voltage power lines, normal electrical equipment, instrument and telecommunication equipments.  .

2. Standard: IEC 60227, IEC 60228, IEC 60332

3. Using Features
     The long-term working temperature of conductor should be not more than 70oC ; fire-resistant cable should be not more than 90oC.
     The environment temperature of cable laying should be not less than 0oC.
     The minimum bending radius of cable should not less than 6 times of its diameter.
Model No.
Conductor
Insulation
Sheath
Feature
Rated Voltage
BV
Copper
PVC
\
\
450/750V
BVR
Copper
PVC
\
Stranded, Flexible
450/750V
NH-BV
Copper
PVC
\
Fire-Resistant
450/750V
RVS
Copper
PVC
\
Stranded, Flexible
300/300V
NH-RVS
Copper
PVC
\
Stranded, Fire-Resistant
300/300V
BVVB
Copper
PVC
PVC
Flat wire
450/750V
RVV
Copper
PVC
PVC
Flexible
300/500V
RVVP
Copper
PVC
PVC
Shield, Flexible
300/500V
WDZ-BYJ
Copper
PE
\
Low Smoke Halogen Free Flame-Retardant
450/750V
WDZ-RYY
Copper
XLPE
PE
Low Smoke Halogen Free Flame-Retardant
300/500V

2017年1月13日星期五

overhead aac bare conductor KS C 3111

overhead aac bare conductor KS C 3111 we get the aac orders from africa clients and will be makng delivery today . thank you . dear clients .

Packaging & Delivery
Packaging Details:
wooden drums, steel drums, steel wooden drums.
Delivery Detail:
Within 20working days

Specifications

We have obtained certificates of ISO9001,ISO14001 China's Electrical Product Safety Certification
Standard:
  ASTM BS DIN GB



Application:
    1. AAC are used in overhead power tranmission and distribution lines with various grade voltages.
    2. Under the same weight, AAC is with higher DC resistance and lower costthan cooper conductor.

The data sheets below show the standards IEC61089:
Code Number
Nominal area
Stranding&
Approx
Approx
Breaking load
DC Resistance at 20
Wire
overall
weight
Diameter
diameter

mm 2
mm
mm
kg/km
kN
ohm/km
10
10
7/1.35
4.05
27.4
1.95
2.8633
16
16
7/1.71
5.12
43.8
3.04
1.7896
25
25
7/2.13
6.4
68.4
4.5
1.1453
40
40
7/2.70
8.09
109.4
6.8
0.7158
63
63
7/3.39
10.2
172.3
10.39
0.4545
100
100
19/2.59
12.9
274.8
17
0.2877
125
125
19/2.89
14.5
343.8
21.25
0.2302
160
160
19/3.27
16.4
439.8
26.4
0.1798
200
200
19/3.66
18.3
549.7
32
0.1439
250
250
19/4.09
20.5
687.1
40
0.1151
400
400
37/3.71
26
1102
64
0.0721
450
450
37/3.94
27.5
1239.8
72
0.0641
500
500
37/4.15
29
1377.6
80
0.0577
560
560
37/4.39
30.7
1542.9
89.6
0.0515
630
630
61/3.63
32.6
1738.3
100.8
0.0458
710
710
61/3.85
34.6
1959.1
113.6
0.0407
800
800
61/4.09
36.8
2207.4
128
0.0361
900
900
61/4.33
39
2483.3
144
0.0321
1000
1000
61/4.57
41.1
2759.2
160
0.0289
1120
1120
91/3.96
43.5
3093.5
179.2
0.0258
1250
1250
91/4.18
46
3452.6
200
0.0231
1400
1400
91/4.43
48.7
3866.9
224
0.0207
1500
1500
91/4.58
50.4
4143.1
240
0.0193